Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C, FSD ... FSF inverters
64 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Set fault number without automatic restart
p1210 Automatic restart mode
Inhibit automatic restart
1 Acknowledge all faults without restarting
4 Restart after line supply failure, without
additional start attempts
6 Restart after fault with additional start at-
14 Restart after line supply failure following
16 Restart after fault following manual
26 Acknowledging all faults and restarting for
Automatic restart, start attempts
Automatic restart, delay time start attempts [s]
Automatic restart, monitoring time [s]
Motor holding brake configuration
No motor holding brake being used
3 Motor holding brake like sequential control,
Motor holding brake, opening time [ms]
Motor holding brake, closing time [ms]
Standstill detection threshold [rpm]
Standstill detection monitoring time [s]
BI: DC braking activation
DC braking below starting speed
DC braking, braking current [A]
Speed at the start of DC braking [rpm]
CO/BO: DC braking status word
p1240 V
DC
controller or V
DC
monitoring configuration
Enable V
DC_max
controller
controller (kinetic buffering)
3 Enable V
DC_min
controller and V
DC_max
con-
controller switch-in level [100 % ≙ p2001]
V
DC_max
controller dynamic factor [%]
p1245 V
DC_min
controller switch-in level (kinetic buffering)
[%]
r1246 V
DC_min
controller switch-in level (kinetic buffering)
p1247 V
DC_min
controller dynamic factor (kinetic buffer-
controller speed threshold [rpm]
V
DC
controller proportional gain
controller integral time [ms]
V
DC
controller rate time [ms]
controller automatic ON level detection
Automatic detection inhibited
Automatic detection enabled
V
DC_min
controller time threshold [s]
controller response (kinetic buffering)
0 Buffer V
DC
until undervoltage, n<p1257 →
1 Buffer V
DC
until undervoltage, n<p1257 →
V
DC_min
controller speed threshold [rpm]
r1258 CO: V
DC
controller output
p1271 Flying restart maximum frequency for the inhibit-
p1280 V
DC
controller or V
DC
monitoring configuration
Enable V
DC_max
controller
Vdc controller configuration
r1282 V
DC_max
controller switch-in level (V/f) [100 % ≙
controller dynamic factor (V/f) [%]
V
DC_max
controller time threshold (U/f) [s]
p1288 V
DC_max
controller ramp-function generator feed-
V
DC
controller proportional gain (U/f)
controller integral time (U/f) [ms]
V
DC
controller rate time (U/f) [ms]
controller speed threshold (U/f) [rpm]