3 Program configuration
Integration of a SINAMICS G120X frequency converter in PCS 7
Entry ID: 109793986, V1.0, 09/2021
16
© Siemens AG
2021 All rights reserved
3 Program configuration
Preface
For quick and easy integration of the drive into the program, this application
example uses the "Drive" template from the Advanced Process Library (APL). The
template already has the blocks "FbDrive" and "MotSpdCl", as well as all the
necessary interconnections. It thus offers a finished automation solution.
The interlock blocks "Interlock", "Permit" and "Protect" have also been added and
wired up. You can delete them if you do not need these functions, depending on
your needs.
After adding the template from the library to the AS program, you need to connect
the input "PZDIn1" at the "FbDrive" block with the first input word "ZSW1" of the
frequency inverter and set a telegram type. The compiler handles the rest of the
signal links.
Figure 3-1
Note
This application example only offers a simple standardized solution to facilitate a
rapid start.
Our support pages have additional application examples and templates for
applications of the SINAMICS G120X.
https://support.industry.siemens.com/cs/search?search=%22SINAMICS%20g12
0X%22&type=ExampleOfUse%2CFaq
Example:
Standard PCS 7 and WinCC/S7 Water Templates for the Water Industry
https://support.industry.siemens.com/cs/ww/en/view/78604785