Integration of a SINAMICS G120X frequency converter in PCS 7
Entry ID: 109793986, V1.0, 09/2021
© Siemens AG
2021 All rights reserved
2. At the block parameter "telegram", configure telegram 20 by changing the
value to "20".
Additional information on the FB "Drive" can be found in the PCS 7 Advanced
Process Library manual.
https://support.industry.siemens.com/cs/ww/en/view/109760968
3.2.3 Process value scaling and units
The speed setpoint "STW2" and the actual speed "ZSW2" are transmitted as
integers in the range 0 to 16384. The normalization of the raw value into a process
value is done in PCS 7 at the driver block "FbDrive".
In the CFC plan in PCS 7 there are a few places that you can perform the
normalization of the process value. They are as follows:
Table 3-3
Upper limit, actual value
Lower limit, actual value
Upper limit for bar graph
Lower limit for bar graph
Unit for labeling on the faceplate
The values PzdIn2m, PZDIn2Scale and PZDIn2Unit are transmitted via the I/Os
"SpeedLink", "SpeedScale" and "SpeedUnit" to the MotSpdCL block.
• Adapt the scaling to suit your application. For G120X applications with pumps
and fans, values in percent or revolutions per minute are recommended.
Table 3-4
Units of measurement in PCS 7 are coded according to the IEC 611582
standard. You can find a full list of all units of measure in the APL manual:
https://support.industry.siemens.com/cs/ww/en/view/109760968/98818690699