EasyManua.ls Logo

Siemens SINAMICS G120X - Symbol Table

Siemens SINAMICS G120X
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Program configuration
Integration of a SINAMICS G120X frequency converter in PCS 7
Entry ID: 109793986, V1.0, 09/2021
17
© Siemens AG
2021 All rights reserved
3.1 Symbol table
1. Open the symbol table.
2. In the "Symbols" column, create the symbolic names for the input and output
tags.
3. Assign the 2 "output words" and 6 "input words" tags to the symbolic names.
The standard telegram type 20 contains the following values:
Table 3-1
Word
Output word
Input word
1
Control word
Status word
2
RPM setpoint
Actual RPM value
3
Motor current
4
Torque
5
Power
6
Namur messages or freely
configurable analog value
Figure 3-2
4. Save the changes and close the symbol table.
5. Open and recompile the hardware configuration.