7.4 Custom Hand mode
Intelligent Operating Panel 2 (IOP-2)
42 Operating Instructions, 06/2020, FW V2.6, A5E39549448B AH
An example of setting up the custom hand mode is given in the instructions below.
Table 7- 1 Interconnection inputs for Status Word 1 in Custom Hand mode
Standard interconnection
r8540 STW 1 from IOP-2 Binector Inputs (BI) p8542 Effective STW1 in Custom Hand
mode
Bit0
ON/OFF key
->
Bit0
ON/OFF1
Bit1
Two quick press of the OFF key
->
Bit1
OFF2
Bit2
A long press of the OFF key
->
Bit2
OFF3
Bit3
Reserved
->
Bit3
Inhibit/enable operation
Bit4
Reserved
->
Bit4
Ramp-function generator enable
Bit5
Reserved
->
Bit5
Continue ramp-function generator
Bit6
Reserved
->
Bit6
Setpoint enable
Bit7
Alarms menu acknowledge all
faults
->
Bit7
Acknowledge faults
Bit8
Jog 1 (Control menu)
->
Bit8
Jog 1
Bit9
Jog 2 (Control menu)
->
Bit9
Jog 2
Bit10
Reserved
->
Bit10
Control by PLC
Bit11
Change direction (Control menu)
->
Bit11
Direction of rotating - reversed
Bit12
Reserved
->
Bit12
Speed control enable
Bit13
Reserved
->
Bit13
Motorized potentiometer, setpoint,
increase
Bit14
Reserved
->
Bit14
Motorized potentiometer, setpoint,
decrease
Bit15
Reserved
->
Bit15
CDS selection
Standard interconnection
r8541
Speed setpoint from IOP-2
Connector Inputs (CI)
p8543
Effective speed setpoint in Custom
Hand mode
N_soll OP
->
Speed setpoint
Setting up Custom Hand mode example
Select Control
Select Custom Hand Mode
Select Custom Hand Mode On