Status signals of the cooling unit
The following status signals are sent from the cooling unit to the converter:
Status signal Function name TM31 terminal
Cooling unit ready
Low = cooling unit not ready
High = cooling unit ready to switch on. You can start
the converter.
DI0 -X520:1
Cooling unit operates correctly.
The cooling unit operates correctly after switch-on.
A pump is running.
The water pressure and the water level match the
specifications.
The coolant temperature lies within the correct
range.
DI1 -X520:2
Group alarm
High = no alarm active
Low = at least one alarm message is active
DI3 -X520:3
Group fault
High = no-fault active
Low = at least one fault is active
DI3 -X520:4
Commissioning
6.2 Commissioning the cooling unit
Applications for Cabinet Modules, liquid cooled
102 Operating Instructions, 04/2015, A5E35974555A