5.3.2 Connecting the motor cable
A Frame sizes FX, GX, HX
B Frame size JX
Figure 5-3 Connecting the motor cables
1. Open
the cabinet. Removed the covers in front of the connection panel for the motor cables
(connections U2/T1, V2/T2, W2/T3; X2).
2. Move or remove the base plate below the connection panel through which the motor cables
are fed.
3. Attach the PE protective conductor at the intended locations in the cabinet to the appropriate
connection with the ground symbol. Observe the torque of 50 Nm for M12.
Electrical connection
5.3 Connection
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A 81