3.6.12 dv/dt filter (option L10)
Pulses at the drive output stress the motor insulation The dv/dt filter is used to limit the voltage
gradient to max. 1 kV/µs. At the same time, the dv/dt filter is used to limit the capacitive
recharging currents of the motor cables, and therefore protects the motor insulation system.
The dv/dt filter is integrated in the power unit.
Drive
Motor
R1,R2,R3 2.5 Ω dv/dt filter resistance
L1, L2,L3 20 μH dv/dt filter reactor
C1,C2,C3 1 μF dv/dt filter capacitor
M Center of the drive
N Center point of the dv/dt filter
Figure 3-10 Circuit diagram option L10
Restrictions when using the output filter
The pulse frequency of the drive must not exceed 200 Hz.
The drive may be operated only with following maximum currents:
4 kA drive: 1680 A (without filter 1750 A)
5 kA drive: 1780 A (without filter 1850 A)
The power loss increases by approx. 30 kW.
The following cable length up to 200 m:
The re-cooling unit requires 10 liter more flow
Description
3.6 Description of options
SINAMICS SM150 6SL3845-2NN41-8AD2
52 Operating Instructions Rev.201910281310 EXAMPLE