Figure 6-4 Grounding lug
6.5.3 Preparations for connecting the power cables
Disconnect the cabinets from the power supply.
Ensure that all the necessary safety measures have been taken at the installation location.
Allow unimpeded access to the cable clamping bar in the cabinets.
6.5.4 Connecting power cables
Contact surface
Figure 6-5 Example: Connecting the power cables
1. Clean the contact surfaces immediately before screwing the connections. Use spirit and a
lintless cloth for cleaning.
2. Apply a thin film of grease. Electrolube 2G is a suitable lubricator.
3. Screw the cable lug with a M12 screw and, if necessary, with a washer to the contact
surface. Tighten the nuts with a torque of 50 Nm.
Electrical connection
6.5 Connection
SINAMICS SM150 6SL3845-2NN41-8AD2
88 Operating Instructions Rev.201910281310 EXAMPLE