Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
122 Operating Instructions, 07/2012, A5E03728167
Parameter Function Range Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
21 Warnings / faults / monitoring
22 Technology controller
P0007 Backlight delay time 0 - 2000 0 U, T - - U16 3
Defines time period after which the backlight of the operator panel display turns off if no buttons have been
pressed.
0 Backlight always on
1 - 2000 Number of seconds after which the backlight turns off.
P0010 Commissioning
parameter
0 - 30 0 T - - U16 1
Filters parameters so that only those related to a particular functional group are selected.
0 Ready
1 Quick commissioning
2 Inverter
29 Download
30 Factory setting
Dependency: Reset to 0 for inverter to run.
P0003 (user access level) also determines access to parameters.
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be
entered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero
automatically.
P0010 = 2
For service purposes only.
P0010 = 30
When resetting the parameters or user default values of inverter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1.
The inverter will automatically reset all its parameters to their default settings.
This can prove beneficial if you experience problems during parameter setup and wish to start again.
Resetting of the user default values will be started by setting parameter P0970 = 21.
The inverter will automatically reset all its parameters to the factory default settings.
Duration of factory setting will take about 60 seconds.
P0011 Lock for user-defined
parameter
0 - 65535 0 U, T - - U16 3
See P0013
P0012 Key for user-defined
parameter
0 - 65535 0 U, T - - U16 3
See P0013

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 Series and is the answer not in the manual?

Siemens SINAMICS V20 Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS V20 Series
CategoryDC Drives
LanguageEnglish

Related product manuals