Parameter list 
  7.2 Parameter list 
SINAMICS V20 Inverter 
Operating Instructions, 07/2012, A5E03728167 
137 
Parameter  Function  Range  Factory 
default 
Can be 
changed 
Scaling  Data 
set 
Data 
type 
Acc. 
Level 
  P1345[0...2] Imax voltage ctrl. prop. gain  x    x  x 
  P1346[0...2] Imax voltage ctrl. integral time  x    x  x 
  P2002[0...2] Reference current  x       
  P2003[0...2] Reference torque  x       
  P2185[0...2] Upper torque threshold 1  x       
  P2187[0...2] Upper torque threshold 2  x       
  P2189[0...2] Upper torque threshold 3  x       
  0  No calculation 
  1  Complete parameterization 
  2  Calculation of equivalent circuit data 
  3  Calculation of V/f control data 
  4  Calculation of controller settings only 
Note:  This parameter is required during commissioning to optimize inverter performance. If there is a large 
mismatch in Power ratings of Inverter to Motor it is possible that r0384 and r0386 may not be calculated 
correctly. In these cases use P1900. 
When transferring P0340, the inverter uses its processor to carry out internal calculations. 
Communications to the inverter may be interrupted.  
The faults can be acknowledged as soon as the calculations have been completed in the inverter. These 
calculations can take approximately 10s to complete. 
P0341[0...2]    Motor inertia [kg*m^2]  0.0001 -  
1000.0  
0.0018  U, T  -  DDS  Float  3 
  Sets no-load inertia of motor.  
Together with P0342 (inertia ratio total / motor) and P1496 (scaling factor acceleration), this value 
produces the acceleration torque (r1518), which can be added to any additional torque produced from a 
BICO source (P1511), and incorporated in the torque control function. 
Dependency:  This parameter is influenced by automatic calculations defined by P0340. 
Note:  The result of P0341 * P0342 is included in the speed controller calculation. 
P0341 * P0342 = total motor inertia  
P1496 = 100 % activates acceleration pre-control for the speed controller and calculates the torque from 
P0341 and P0342. 
P0342[0...2]    Total / motor inertia ratio  1.000 - 
400.00 
1.000  U, T  -  DDS  Float  3 
  Specifies ratio between total inertia (load + motor) and motor inertia. 
Dependency:  See P0341 
P0344[0...2]    Motor weight [kg]  1.0 - 
6500.0 
9.4  U, T  -  DDS  Float  3 
  Specifies motor weight [kg]. 
Dependency:  See P0341 
Note:  This value is used in the motor thermal model. It is normally calculated automatically from P0340 (motor 
parameters) but can also be entered manually. Default value is depending on inverter type and its rating 
data. 
r0345[0...2]    Motor start-up time [s]  -  -  -  -  DDS  Float  3 
  Displays motor start-up time. This time corresponds to the standardized motor inertia. The start-up time is 
the time taken to reach rated motor speed from standstill at acceleration with rated motor torque (r0333).