Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
180 Operating Instructions, 07/2012, A5E03728167
Parameter Function Range Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
P1320[0...2] Programmable V/f freq.
coord. 1 [Hz]
0.00 -
599.00
0.00 T - DDS Float 3
Sets the frequency of the first point of V/f coordinates (P1320 / 1321 to P1324 / 1325) to define V/f
characteristic. These parameter pairs can be used to provide correct torque at correct frequency.
Dependency: To set parameter, select P1300 = 3 (V/f with programmable characteristic). The acceleration boost and
starting boost defined in P1311 and P1312 are applied to V/f with programmable characteristic.
Note: Linear interpolation will be applied between the individual data points.
V/f with programmable characteristic (P1300 = 3) has 3 programmable points and 2 non-programmable
points. The 2 non-programmable points are:
Continuous boost P1310 at 0 Hz
Rated motor voltage P0304 at rated motor frequency P0310
P1321[0...2] Programmable V/f volt.
coord. 1 [V]
0.0 -
3000.0
0.0 U, T - DDS Float 3
See P1320
P1322[0...2] Programmable V/f freq.
coord. 2 [Hz]
0.00 -
599.00
0.00 T - DDS Float 3
See P1320
P1323[0...2] Programmable V/f volt.
coord. 2 [V]
0.0 -
3000.0
0.0 U, T - DDS Float 3
See P1320
P1324[0...2] Programmable V/f freq.
coord. 3 [Hz]
0.00 -
599.00
0.00 T - DDS Float 3
See P1320
P1325[0...2] Programmable V/f volt.
coord. 3 [V]
0.0 -
3000.0
0.0 U, T - DDS Float 3
See P1320
P1330[0...2] CI: Voltage setpoint - 0 T - CDS U32 /
Float
3
BICO parameter for selecting source of voltage setpoint for independent V/f control (P1300 = 19).
P1333[0...2] Start frequency for FCC
[%]
0.0 - 100.0 10.0 U, T PERCEN
T
DDS Float 3
Defines start frequency at which FCC (flux current control) is enabled as [%] of rated motor frequency
(P0310).
Notice: If this value is too low, the system may become unstable.
P1334[0...2] Slip compensation
activation range [%]
1.0 - 20.0 6.0 U, T PERCEN
T
DDS Float 3
To set the frequency activation range for slip compensation. The percentage value of P1334 refers to the
motor rated frequency P0310.
The upper threshold will always stay 4 % above P1334.
5DQJHRIVOLSFRPSHQVDWLRQ
ZLWKVOLSFRPSHQVDWLRQ
ZLWKRXWVOLSFRPSHQVDWLRQ
I
RXW
I
I
I
RXW
1
I
1
I
1
VHW
3
3

3
3
3
Dependency: Slip compensation (P1335) active.

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 Series and is the answer not in the manual?

Siemens SINAMICS V20 Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS V20 Series
CategoryDC Drives
LanguageEnglish

Related product manuals