Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
50 Operating Instructions, 07/2012, A5E03728167
Parameter Description Factory
default
Default for
Cn008
Remarks
P0731[0] BI: Function of digital output 1 52.3 52.2 Inverter running
P0732[0] BI: Function of digital output 2 52.7 52.3 Inverter fault active
Connection macro Cn009 - PID control with the fixed value reference
OK
M
10V AI1 AI2 0V DI1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1 + DO1 - P + N-
DO2
0V 0V
0~20mA=
0~50 /60 Hz
220V
N
212))
PID controller
$FWXDOYDOXH
)L[HG3,'VHWSRLQW
)L[HG3,'VHWSRLQW
)L[HG3,'VHWSRLQW
)DXOW5XQQLQJ6SHHG
aP$
Connection macro settings:
Parameter Description Factory
default
Default for
Cn009
Remarks
P0700[0] Selection of command source 1 2 Terminals as command source
P0701[0] Function of digital input 1 0 1 ON / OFF
P0702[0] Function of digital input 2 0 15 DI2 = PID fixed value 1
P0703[0] Function of digital input 3 9 16 DI3 = PID fixed value 2
P0704[0] Function of digital input 4 15 17 DI4 = PID fixed value 3
P2200[0] Enable PID controller 0 1 Enable PID
P2216[0] Fixed PID setpoint mode 1 1 Direct selection
P2220[0] BI: Fixed PID setpoint select bit 0 722.3 722.1 BICO connection DI2
P2221[0] BI: Fixed PID setpoint select bit 1 722.4 722.2 BICO connection DI3
P2222[0] BI: Fixed PID setpoint select bit 2 722.5 722.3 BICO connection DI4
P2253[0] CI: PID setpoint 0 2224 PID setpoint = fixed value
P2264[0] CI: PID feedback 755.0 755.1 PID feedback = AI2