Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
54 Operating Instructions, 07/2012, A5E03728167
Parameter Description Factory
default
Default for
AP020
Remarks
P1080[0] Minimum frequency 0 20 Inverter running at a lower speed
inhibited
P1120[0] Ramp-up time 10 10 Ramp-up time from zero to
maximum frequency
P1121[0] Ramp-down time 10 20 Ramp-down time from maximum
frequency to zero
Application macro AP021 - Compressor applications
Parameter Description Factory
default
Default for
AP021
Remarks
P1300[0] Control mode 0 0 Linear V/f
P1080[0] Minimum frequency 0 10 Inverter running at a lower speed
inhibited
P1312[0] Starting boost 0 30 Boost only effective when
accelerating for the first time
(standstill)
P1311[0] Acceleration boost 0 0 Boost only effective when
accelerating or braking
P1310[0] Continuous boost 50 50 Additional boost over the complete
frequency range
P1120[0] Ramp-up time 10 10 Ramp-up time from zero to
maximum frequency
P1121[0] Ramp-down time 10 10 Ramp-down time from maximum
frequency to zero
Application macro AP030 - Conveyor applications
Parameter Description Factory
default
Default for
AP030
Remarks
P1300[0] Control mode 0 1 V/f with FCC
P1312[0] Starting boost 0 30 Boost only effective when
accelerating for the first time
(standstill)
P1120[0] Ramp-up time 10 5 Ramp-up time from zero to
maximum frequency
P1121[0] Ramp-down time 10 5 Ramp-down time from maximum
frequency to zero