Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
58 Operating Instructions, 07/2012, A5E03728167
Parameter Function Setting
P1082[0] Maximum frequency [Hz] Range: 0.00 ... 599.00 (factory default: 50.00)
Note:
The value set here is valid for both clockwise and counter-
clockwise rotation
P1120[0] Ramp-up time [s] Range: 0.00 ... 650.00 (factory default: 10.00)
Note:
The value set here means the time taken for motor to accelerate
from standstill up to the maximum motor frequency (P1082)
when no rounding is used.
P1121[0] Ramp-down time [s] Range: 0.00 ... 650.00 (factory default: 10.00)
Note:
The value set here means the time taken for motor to
decelerate from the maximum motor frequency (P1082) down to
standstill when no rounding is used.
P1300[0] Control mode = 0: V/f with linear characteristic (factory default)
= 1: V/f with FCC
= 2: V/f with quadratic characteristic
= 3: V/f with programmable characteristic
= 4: V/f with linear eco
= 5: V/f for textile applications
= 6: V/f with FCC for textile applications
= 7: V/f with quadratic eco
= 19: V/f control with independent voltage setpoint
P3900 End of quick commissioning = 0: No quick commissioning (factory default)
= 1: End quick commissioning with factory reset
= 2: End quick commissioning
= 3: End quick commissioning only for motor data
Note:
After completion of calculation, P3900 and P0010 are
automatically reset to their original value 0.
The inverter displays "8.8.8.8.8" which indicates that it is busy
with internal data processing.
P1900 Select motor data identification = 0: Disabled
= 2: Identification of all parameters in standstill