EasyManua.ls Logo

Siemens SINAMICS V20 Series - Page 65

Siemens SINAMICS V20 Series
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
65
Parameter Boost type Description
P1310 Continuous boost [%] This parameter defines boost level relative to P0305 (rated motor current)
applicable to both linear and quadratic V/f curves.
Range: 0.0 ... 250.0 (factory default: 50.0)
The voltage boost is effective over the complete frequency range whereby the
value continually decreases at high frequencies.
/LQHDU9I
2XWSXWYROWDJH
9
9
PD[
I
PD[
9
&RQ%RRVW
9
Q
I
Q
3
3
3
I
P1311 Acceleration boost [%] This parameter applies boost relative to P0305 (rated motor current) following
a positive setpoint change and drops back out once the setpoint is reached.
Range: 0.0 ... 250.0 (factory default: 0.0)
The voltage boost is only effective when accelerating or braking.
2XWSXWYROWDJH
1RUPDO9I
5)*
DFWLYH
9
9
Q
3
I
Q
3
I
PD[
3
I
9
$FF%RRVW
9
PD[
I
VHW

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Related product manuals