Configuring
6.3 Configuring the 3RW5 Soft Starter
SIRIUS 3RW5 Modbus communication module
86 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
6.3.2.6 Silent interval time
Setting options
3RW5 HMI High Feature
Menu: "Parameter > Communication module > Modbus RTU > Silent interval time"
You will find more information on operating the 3RW5 HMI High Feature in the
Equipment Manual of the 3RW5 soft starter.
User program via the "Modbus RTU communication parameters" data table (Page 177)
Parameters
Parameter
Description
Silent interval time The silent interval time is the interval between 2 Modbus telegrams.
For the setting "Automatic" (factory setting), the minimum silent
interval time of the baud rate used is automatically set. For example,
2 ms for the baud rate 19.2 kbit/s. You will find the setting range of the
silent interval time in chapter Modbus RTU communication parameters
(Page 177).