Technical data
6.2 Output
SITOP PSU100L
Manual, 08.2016, C98130-A7603-A1-2-7629
37
Figure 6-6 6EP1336-1LB00 output characteristic
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced. When the output
voltage falls below approx. 10 V, the device switches off, and automatically restarts (see
Figure 6-3 Output characteristic 6EP1332-1LB00 (Page 36) and Figure 6-4 Output
characteristic 6EP1333-1LB00 (Page 36)). This behavior is repeated as long as the overload
condition is present (only for 6EP1332-1LB00 and 6EP1333-1LB00). The 6EP1334-1LB00
device has a U-I characteristic (see Figure 6-5 Output characteristic 6EP1334-1LB00
(Page 36)) The 6EP1336-1LB00 device has a U-I characteristic (see Figure 6-6 6EP1336-
1LB00 output characteristic (Page 37))