Technical data
6.2 Output
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
57
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
Duration of the overload
capability for an overcurrent
condition caused by a short
circuit in operation.
• Remark
25 ms
per 1 min
25 ms
per 1 min
25 ms
per 1 min
Can be connected in parallel
to increase the power rating
• Remark
Yes
Switchable characteristic
curve with switch A (see
Figure 2-5
Operating display
Yes
Switchable characteristic
curve with switch A (see
Figure 2-5
Operating display
Yes
Switchable characteristic
curve with switch A (see
Figure 2-5
Operating display
Number of devices that can
be connected in parallel to
increase the power rating,
2 2 2
Overload capability (Extra
30 A for 5 s/min 60 A for 5 s/min 60 A for 5 s/min
Output characteristic see Figure 6-3 Output char-
acteristic curve 6EP3436-
8SB00-0AY0 single opera-
see Figure 6-8 6EP1437-
3BA10 single operation out-
put characteristic curve
see Figure 6-9 Output char-
acteristic 6EP3437-8SB00-
0AY0 single operation
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
Output Regulated, isolated DC
voltage
Regulated, isolated DC
voltage
Regulated, isolated DC
voltage
Rated voltage U
out rated
DC 36 V 48 V 48 V
Total tolerance, static ± 3 % 3 % 3 %
Static line regulation, approx.
Static load regulation,
0.2% 0.2% 0.2 %
Residual ripple in the load
range
100 mV 100 mV 100 mV
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
200 mV 200 mV 200 mV
Adjustment range 36 - 42 V 42 - 56 V 46 - 56 V
for U
in
< 360 V: 46 - 52 V
Output voltage can be ad-
Yes Yes Yes
Output voltage setting
• Remark
Via potentiometer
Max. 480 W
Via potentiometer
Max. 480 W
Via potentiometer
Max. 960 W
LED green for "36 V O.K."
LED green for "48 V O.K."
LED green for "48 V O.K."