MAG 8000 & MAG 8000 CT
11
SFIDK.PS.026.D9.02
Pulse output connection
diagram for MAG 8000 &
MAG 8000 CT
The pulse output can be configured as volume, alarm or call-up, see section 4 Commissioning.
Pulse output is not polarized and can be connected for positive or negative logic.
R = pull up/down resistor is selected in relation to the V power supply and with at max. current
I of 50 mA.
Pulse output must be connected to equipment complying with Low Voltage Directive in order
to be considered safe. The isolation within MAG 8000 & MAG 8000 CT pulse output is only a
functional isolation.