F US Clamp-on Communications Module Kit Installation
SITRANS F US Clamp-on Communications Module
12 Hardware Installation Instructions, 03/2015, A5E32586525-AE
6. Place the Communications Module over the I/O Module and align connector J3 with P1 of
the I/O Module (figure 3-2).
Ethernet Connector J5
RS-485 Connector J1
SW1
Captive Screw and Standoff
SW2
Standoff
J3
Figure 3-2 SITRANS F US Clamp-on Communications Module A5E31949269
7. Gently press the Communications Module down to connect it to the I/O Module.
8. Tighten the captive screws to secure the Communications Module and I/O Module.
9. If using Ethernet IP, connect the Ethernet connector.
Note
Ethernet Web Utility Discovery.zip
This Web utility is used to locate communications modules on the same network.
The web utility can be found at
http://www.fieldserver.com/techsupport/utility/
downloads.php
(
http://www.fieldserver.com/techsupport/utility/downloads.php. //
XmlEditor.InternalXmlClipboar
d:6489c307-3482-c2fd-cc08-262dd24d5093).
(Discovery.zip)
The default IP address is: 192.168.0.2
10.If using RS485, connect RS-485 connector to J1.
11.Referring back to figure 3-1, after Communications Module installation is complete, place
the new Communications Module cover supplied in the mounting kit over the board and
tighten the captive screw
.
12.Close the flow meter cover and secure the side latch.