A5E32106153 SITRANS Probe LR – MISE EN SERVICE SIMPLIFIEE Page FR-3
mmmmm
Français
Alimentation électrique
• Max. 30 VCC
• 4 à 20 mA
Agréments
• Exploitation généraleCSA
US/C
, FM, CE, C-TICK
• Radio Europe (R&TTE), FCC, Industry Canada
•Zone
dangereuse Sécurité intrinsèque (Europe) ATEX II 1 G EEx ia IIC T4
(US/Canada) FM/CSA
1
: (barrière requise)
Class I, Div. 1, Gr. A, B, C, D
Class II, Div 1, Gr. E, F & G
Class III T4
(Australie) ANZEx Ex ia IIC T4
(Tamb = –40 à + 80 °C) IP67, IP68
(International) IECEx TSA 04.0020X Ex ia IIC T4
(Brazil) INMETRO: DNV 12.0068 X
Ex ia IIC T4 Ga
IP66/IP67/IP68
-40 ºC
≤ T a ≤ +80 ºC
DNV #OCP 0017
ABNT NBR IEC 60079-0:2008 e
ABNT NBR IEC 60079-11:2009
Non-incendiaire (USA) FM
2
:
Class I, Div. 2, Groupes A, B, C, D, T5
• Marine Lloyd’s Register of Shipping
Certification ABS (American Bureau of Shipping)
Construction
• Raccords process :
raccord fileté 1.5” NPT, BSP, ou G (BS EN ISO 228-1)
• Antenne :
tige polypropylène construction hermétique
Nominale 24 VCC, max. 550 Ohms
1.
Voir
Wiring Drawing: Intrinsically Safe (FM )
page 2, Annexe A, pour le dessin réf. 23651611, ou
Wiring
Drawing: Intrinsically Safe (CSA)
page 3, Annexe A, pour le dessin réf. 23651621.
2.
Voir
Wiring Drawing: Non-incendive (FM)
page 1, Annexe A, dessin réf. 23650537.
Note : Utiliser des presse étoupes adaptés pour garantir l’étanchéité dans les applications
Type 4X/NEMA 4X, Type 6/NEMA 6, IP67, IP68 (montage en extérieur).
Note : le SITRANS Probe LR a été testé en conformité avec la norme EN61000-4-3 (CEM
CE), installé sur une cuve métallique.