What to do if the PLC value is not equal to the displayed value on Siemens Sitrans LR250 Transmitter?
- SShannon PonceAug 26, 2025
If the PLC value doesn't match the displayed value on your Siemens LR250 Transmitter, verify you are looking at the right spot in the PLC. Also, ensure scaling hasn't been programmed into the PLC, as all scaling should be performed by the LR250. Finally, check the network to confirm the PLC is communicating with the LR250.