Page EN-16 SITRANS Probe LU (PROFIBUS PA) – QUICK START MANUAL A5E32081626
mmmmm
English
PROFIBUS Current Consumption
Allows you to select the PROFIBUS device current. Higher values allow faster update rates.
1
Go to Input > Standard Setup > PROFIBUS Current Consumption, and enter the value
corresponding to the desired device current.
Maintenance
SITRANS Probe LU requires no maintenance or cleaning.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
Warning: This parameter should be modified only once at installation, to match the design
criteria of the network.
Values Loop current
Update time
1
0*12 mA 6.0 s (typical), maximum 16.0 s
1 13 mA 5.0 s (typical), maximum14.0 s
2 15 mA 3.7 s (typical), maximum8.0 s
3 20 mA 2.4 s (typical), maximum4.0 s
1.
Temperature dependent: typical value at +20 °C (+68 °F); maximum value at +80 °C (+176 °F).