EasyManua.ls Logo

Siemens sitrans PROBE LU - Remote Operation via PROFIBUS PA; SIMATIC PDM Software; Device Description File

Siemens sitrans PROBE LU
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page A-4 SITRANS Probe LU (PROFIBUS PA) – QUICK START MANUAL A5E32081626
mmmmm
A: Connection Drawings
Product Group
FOR INTERNAL
USE ONLY
S. NGUYEN
PETERBOROUGH
E. DeSIMONE
R. CLYSDALE
1:1
44
NTS
A
1
Hazardous (Classified) Location
Non-Hazardous Location
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III
T4 @ T
a
= – 40°C to + 80°C
Intrinsic safety barrier
Notes:
1. The non-intrinsically safe terminals (power rail) must not be connected to any device which uses or generates more
than 250 Vrms or dc unless it has been determined that the voltage has been adequately isolated.
2. In the USA the installation must meet the requirements of the National Electrical Code, NFPA 70. article 504 resp.
article 505 and ANSI / ISA RP 12.6 . In Canada observe the Canadian Electrical Code.
3. Multiple earthing of screen is allowed only, if high integrity equipotential system is realized between the points of bonding.
For Intrinsic safety application use CSA / FM
approved associated apparatus or barrier
Entity parameters:
Entity parameters:
V or V 24 V
I
oc t
s
£
ct
ot
a cable
a cable
or I 250 mA
P or P 1.2 W
C 1.0 nF + C
L 0+L
£
£
³
³
Terminals and
U , V = 24 V
I , I = 250 mA
P , P = 1.2 W
C = 1.0 nF
L=0
imax
imax
imax
i
i
See Note 1
V
V
SITRANS
Probe LU
(PROFIBUS PA)
2365061701
18 / APRIL / 2005
ULTRASONICS
SITRANS Probe LU
PROFIBUS PA
CONNECTION DRAWING
23650617
SEE SHEET 1

Other manuals for Siemens sitrans PROBE LU

Related product manuals