7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 105
mmmmm
J: Hazardous installation
EU Equivalency
Any zener diode safety barrier, certified by an EU approved certification body to
[ EEx ia ] IIC, its output voltage (U
o
) not exceeding 24 V and its output current (I
o
) limited
by load resistance (R
o
); such that I
o
= U
o
/ R
o
, does not exceed 250 mA.
Notes
The installation must comply with national requirements.
The safe area is unspecified except that it must not be supplied from nor contain,
under normal or abnormal conditions, a source of potential with respect to earth in
excess of 250 V rms or 250 V DC.