Remote Operation : PA
7ML19985JB02 SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL Page 29
Values of the DIAGNOSIS bit:
0 = not set
1 = set
0x00010000
1
0 Zero point error (limit position) R
0x00020000 1
Power supply failure (electrical, pneu-
matic)
R
0x00040000 2 Configuration invalid R
0x00080000 3 New startup carried out (Warm Start) A
0x00100000 4 Restart carried out (Cold Start) A
0X00200000 5 Maintenance required R
0X00400000 6 Characterization invalid R
0X00800000 7
Set to 1 (one), if the Ident_Number of the
running cyclic data transfer and the value
of Physical Block
IDENT__NUMBER_SELECTOR parame-
ter are different.
R
2 0 to 7 Reserved for use within the PNO
b
3
0 to 6 Reserved for use within the PNO
0X00000080 7 More diagnosis information is available
a.
R indicates the message remains active as long as the reason for the message
exists.
A indicates the message will automatically reset after 10 seconds.
b.
PNO – PROFIBUS User Organization
Hex values Byte Bit Description
Indication
class
a
(cont’d)