Commissioning 
  6.3 Adjustment and initial commissioning 
SIWAREX WL200 
Operating Instructions, 07/2016, A5E02199611B-03 
35 
 
General procedure for corner load adjustment 
The load cells are passive sensors: You should therefore follow the instructions in the 
manual for the weighing module primarily. When they are installed in hazardous areas, the 
instructions for the Ex i interface or for the Ex barrier must also be followed.  
When the corner load for a scale has to be checked, impermissibly large deviations in the 
weight indication can occur in the case of load cells that are not current-calibrated.  
The corner load errors can be electrically compensated. This is done by matching the 
individual measured values to the smallest measured value by connecting additional 
resistors. For details of how to do this see section Example for corner load adjustment 
(Page 35)  
The resistors are connected in series with the load cell measuring signal. The appropriate 
resistor will reduce the measuring voltage until it is equal to the smallest voltage. The 
temperature coefficient must be suitably small, due to connection of the resistors in the 
measuring circuit: 0.25 ppm/K to 10 ppm/K.  
 
Example for corner load adjustment 
Example data for corner load adjustment 
The corner load adjustment described below as an example is based on the following data: 
 
Scale 
Platform scale with 4 load cells 
Rated load 
500 kg 
Rated 
character-
istic value 
2.0 mV/V 
Figure 6-2  Test process / scale