6 - USE
Parameter Description
Access
level
Adjustment
range
Default value
Custom
value
Parameters
User
System control
Antifreeze = TutorBit ignores all heating requests and only runs the Antifreeze function;
Heating = TutorBit works normally for the set heating requests, also set together with HP.
Cooling = Tutorbit works in connection with a heat pump to make cooling.
Installer
Antifreeze;
Heating;
Cooling;
Modules
Heat generator operating parameters Installer
Casc. setp offsetup Increase of the module setpoint with respect to the general cascade sensor setpoint
Installer 0...20 5 K
Start hyst Temperature differential on the cascade setpoint when heat generators are switched on
Installer 0...20 5 K
Stop hyst Temperature differential on the cascade setpoint when heat generators are switched off
Installer 0...20 5 K
Light-on delay Module switch-on delay time
Installer 0...900 180 s
Switch-off delay Module switch-off delay time
Installer 0...900 180 s
Modulation delay Delay time to modulation of the modules on the cascade setpoint
Installer 0...20 4 min
PID propor. band Proportional band of the generator output adjustment PID for controlling the cascade setpoint
Factory 0...100 40 °C
PID integral time Integral band of the generator output adjustment PID for controlling the cascade setpoint
Factory 0...900 80 s
All Off Hyst Cascade setpoint differential of switch-off of all modules
Installer 0...25 7.0 K
Spring Temp. Spring temperature for switch-off of the module and HP heating function. This parameter is only implemented
when a heating circuit is controlled by an outdoor reset (Conguration>Zones>Zone Mode> Outd Reset-RT/
Outd Reset comp-RT/ Outd Reset-RS)
Installer 10...40 21 °C
Modules setpoint incr. Increase or decrease gradient of the modules setpoint
Installer 0.1...20 2.0 d°C/s
Autumn Temp. COOL function shutdown temperature for HP
Installer 10...40 28°C
DHW DHW operating parameters
User
DHW Setpoint Hot water tank setpoint
User 35...90 50 °C
DHW action Manual = operation according to the setpoint;
Automatic = operation according to the weekly programme;
Off = DHW service switched off;
User
Manual;
Automatic;
Off;
Manual
Time program DHW time programme
Installer
Reset Delete time programme
Installer No...Yes No
Copy Copy time programme command
Installer No...Yes No
From: Selection of the rst day to start copying
Installer
Monday...
Sunday
Monday
To: Selection of the last day to end copying
Installer
Monday...
Sunday
Monday
Monday Start Stop
06:00 8:00
12:00 14:00
18:00 22:00
Setting the 3 operating time slots on Monday, Tuesday, Wednesay,Thursday and Friday.
Installer
Time program
Installer
Saturday Start Stop
06:00 8:00
12:00 14:00
18:00 22:00
Setting the 3 operating time slots on Saturday.
Installer
Sunday Setting the 3 operating time slots on Sunday.
Installer