Parameter Description
Access
level
Adjustment
range
Default value
Custom
value
Cool Supply Setp Fixed setpoint manually adjusted for cooling. Visible only if Conguration>Zones>Zone mode 1 = FixSp-RT/
FxSp-Comp.RT
User 5...90 18°C
Cool Night setback Raising the cooling supply temperature generated by the opening of the RT. Visible only if
Conguration>Zones>Zone mode 1 = Outd Reset comp-RT/ FxSp-Comp.RT.
Installer 0...20 10°C
Heating Outdoor reset Operating parameters of the outdoor reset for Zone 1
Installer
Slope Slope of the curve
Installer 0.1...4 2.5
Sliding Curve slippage
Installer -10...10 0 K
Min Temp. Minimum setpoint temperature for Zone 1
Installer 20...55 20 °C
Max Temp. Maximum setpoint temperature for Zone 1
Installer 20...90 75 °C
Cooling Outdoor reset Operating parameters of the outdoor reset for Zone 1
Installer
Set Minimum Minimum cooling supply temperature
Installer 3...30 3°C
Set Maximum Maximum cooling supply temperature
Installer 5...30 12°C
T. Ext 25 Set Cooling supply temperature when outdoor temperature is 25°C
Installer 5...30 9°C
T. Ext 35 Set Cooling supply temperature when outdoor temperature is 35°C
Installer 5...30 11°C
Heating Timer program Heating Timer program for Zone 1, only if Parameters>Zones>Action=Automatic
Installer
Reset Delete time programme
Installer No...Yes No
Copy Copy time programme command
Installer No...Yes No
From: Selection of the rst day to start copying
Installer
Monday...
Friday
Monday
To: Selection of the last day to end copying
Installer
Monday...
Friday
Monday
Monday Start Stop
06:00 8:00
12:00 14:00
18:00 00:00
Setting the 3 operating time slots on Monday, Tuesday, Wednesay,Thursday and Friday.
Installer
Off
Reduced
Comfort
Precomfort
Heating Timer program
Installer
Saturday Start Stop
06:00 8:00
12:00 14:00
18:00 22:00
Setting the 3 operating time slots on Saturday and Monday
Installer
Cooling Timer program Cooling Timer program for Zone 1, only if Parameters>Zones>Action=Automatic
Installer
Reset Delete time programme
Installer No...Yes No
Copy Copy time programme command
Installer No...Yes No
From: Selection of the rst day to start copying
Installer
Monday...
Friday
Monday
To: Selection of the last day to end copying
Installer
Monday...
Friday
Monday

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TUTORbit POL895 and is the answer not in the manual?

Siemens TUTORbit POL895 Specifications

General IconGeneral
BrandSiemens
ModelTUTORbit POL895
CategoryController
LanguageEnglish

Related product manuals