6 - USE
Monday Start Stop
06:00 8:00
12:00 14:00
18:00 00:00
Setting the 3 operating time slots on Monday, Tuesday, Wednesay,Thursday and Friday.
Installer
Off
Reduced
Comfort
Precomfort
Cooling Timer program
Installer
Saturday Start Stop
06:00 8:00
12:00 14:00
18:00 22:00
Setting the 3 operating time slots on Saturday and Monday
Installer
Zone2 Heating circuit 2 (submenu equal to Zone 1)
User
Zone3 Heating circuit 2 (submenu equal to Zone 1)
User
Zone4 Heating circuit 2 (submenu equal to Zone 1)
User
Zone5 Heating circuit 2 (submenu equal to Zone 1)
User
Anti-legionella Anti-legionella setting parameters for the DHW tank
Installer
Frequence Cycle frequency
Installer 1...30 7 days
Light-on hour Cycle start time
Installer 0...23 6 h
Setpoint Hot water tank lling setpoint during the anti-legionella cycle
Installer 50...70 65 °C
Max light-on delay Maximum time for reaching the anti-legionella setpoint
Installer 1...360 30 min
Hold on timer Minimum time for maintaining the anti-legionella temperature
Installer 1...360 15 min
Output rotation Rotation of the heat generators
Installer
Heating Rotation of the heat generators assigned to the “Heating” service
Installer
Mode Type of rotation: Fixed = rotation on a time basis;
Absent = no rotation;
Timed = Rotation based on the ageing time;
Installer
Fixed;
Absent;
Timed;
Fixed
Fix Rotation “Fix rotation” parameters
Installer
Interval Time for the next rotation
Installer 0...15 6 days
Base time rotation “Base time rotation” parameters
Installer
Max ancient diff Maximum ageing time of a heat generator after which rotation occurs.
Installer 0...10 6 days
DHW Rotation of the heat generators assigned to the “DHW” service
Installer
Mode Type of rotation: Fixed = rotation on a time basis;
Absent = no rotation;
Timed = Rotation based on the ageing time;
Installer
Fixed;
Absent;
Timed;
Fixed
Fix Rotation “Fix rotation” parameters
Installer
Interval Time for the next rotation
Installer 0...15 6 days
Base time rotation “Base time rotation” parameters
Installer
Max ancient diff Maximum ageing time of a heat generator after which rotation occurs.
Installer 0...10 6 days
Outdoor temperature Outdoor sensor parameters
Installer
Building type Delay generated by the building’s insulation before an external temperature variation affects the room
temperature
Installer 0...20 0 hs
Actual Actual outdoor temperature
Installer Value Value