6 - USE
Parameter Description
Access
level
Adjustment
range
Default value
Custom
value
Compound (OutReset) Outdoor temperature lessened by the “Building type”
Installer Value Value
Soft (Spring) Outdoor temperature lessened by the “Building type” for the spring period
Installer Value Value
DHW Priority Management of DHW/heating priority
Installer
Module T. hyst
Installer
Pump lock offsetup Negative differential with respect to the hot water tank setpoint, after which the heating is switched off.
Installer 0...20 10 K
Pump unlock offsetup Negative differential with respect to the hot water tank setpoint, after which the heating is switched on.
Installer 0...20 5 K
Antifrost function Antifreeze function parameters
Installer
Outdoor T. Outdoor temperature value
Installer Value Value
Circulation Setpoint Outdoor temperature below which the circuit pumps switch on
Installer -10...20 5.0 °C
Circ Setp hyst Hysteresis on the outdoor switch-on and off temperature of the circuit pumps
Installer 0...10 1.0 K
Heating Setp Outdoor temperature below which the heat generators switch on
Installer -10...20 1.0 °C
Heat Setp hyst Hysteresis on the outdoor switch-on and off temperature of the heat generators
Installer 0...10 1.0 K
Frequence Frequence of the heat generators switch-on cycles
Installer 0...1000 2.0 h
Timer Heat generators switch-on duration
Installer 0...200 10 min
Solar Solar parameters
Installer
Solar pump DT On Differential between the solar panel and solar hot water tank temperature above which the solar pump
switches on
Installer 4...64 8.0 K
Solar pump dT Off
Differential between the solar panel and solar hot water tank temperature below which the solar pump switches off
Installer 2...10 4.0 K
Min Temp. Minimum temperature of the solar panel below which the solar pump always remains off
Installer 5...60 20 °C
Max Temp. Maximum temperature of the hot water tank above which the solar pump remains off
Installer 40...70 60 °C
Max load hyst Maximum temperature increase of the solar hot water tank during the anti-stagnation cycle
Installer 3...15 5 °C
Antistagn On Temp Solar panel temperature when anti-stagnation cycle starts
Installer 100...120 105 °C
Antistagn Off Temp. Maximum solar panel temperature after which the anti-stagnation cycle is switched off to prevent cavitation to
the solar pump
Installer 120...140 120 °C
Antistagn Hysteresis Negative hysteresis with respect to the “Antistagn On temp.” to switch-off the anti-stagnation cycle
Installer 5...15 10 K
Antifrost Setpoint Solar panel temperature for activating the antifreeze cycle on the solar panel
Installer -10...140 4.0 °C
Antif hysteresis Positive hysteresis to switch-off the antifreeze cycle on the solar panel
Installer 2...10 4 K
Room Unit data n QMX3 room sensor settings, visible only if Conguration>Zones>Zone Mode n = Outd Reset-RS/ FixSp-RS
Installer
SN Serial number of room unit connected
Installer Value Value
Temperature Temperature read con room unit
Installer Value Value
Operative mode Operative mode of Heating/Coolin circuit
Installer
Auto, Comfort,
Precomfort,
Reduced,
Protected
Setpoint Actual setpoint circuit
Installer Value Value
Comfort Setpoint Heating Band settings for QMX3 Room sensor
Installer 8...40 Value
Heating Precomfort Set Band settings for QMX3 Room sensor
Installer 8...40 Value