Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-1513
Figure 7
ZIC-4A Supervised Municipal Tie Wiring
12345678
910111213141516
+
+
-
+
-
+
-
+
-
+
-
17 18 19 20 21 22 23 24
ZONE 1
INPUT
ZONE 2
INPUT
ZONE 3
INPUT
ZONE 4
INPUT
ONE SLOT OF CC-5
MUNICIPAL
TIE
ZONE 1
24K,
1W
5%
4321
4321
LLM-1
TB1
TB2
-
DO NOT USE
DO NOT USE
NOTES
 1. All wiring must be in
accordance with
Article 760 of NEC
or local building codes.
 2. All output circuits are
not power limited.
 3. Electrical Ratings:
Trip Coil: 14.5 ohms
Trip Current:
220mA to 320mA DC
Supervisory Current:
1mA DC
Voltage: 24V nominal
 4. EOL resistor, 24k ohms,
1 watt, 5%, P/N 140-820405.
 5. Polarity shown in active state.
 6. Supervised for open circuit only.
 7. LLM-1 module is required. The total
loop resistance from the LLM-1 to
the Municipal Tie, including the
14.5 ohms in the Municipal Tie,
should not exceed 22.5 ohms.
 8. Wire jumper must be connected
between the positive terminals
at the output.
 9. Any circuit may be used.
10. Minimum Emergency Power:
60 hours standby
5 minute alarm
11. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB
(P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
12. Positive or negative ground fault detected at <40K ohms for terminals 1-16.
Figure 8
ZIC-4A Leased Line Wiring
12345678
910111213141516
+
+
+
+
+
+
+
+
-
-
+
-
+
-
+
-
17 18 19 20 21 22 23 24
ZONE 1 & 2
INPUT
ZONE 3
INPUT
ZONE 4
INPUT
ONE SLOT OF CC-5
LEASED
LINE
ZONE 1
LEASED
LINE
ZONE 3
4321
4321
LLM-1
NC
NC
NC
NC
NC
NC
NC
NC
TB1
TB2
4321
4321
LLM-1
TB1
TB2
4321
4321
LLM-1
TB1
TB2
LEASED
LINE
ZONE 2
LEASED
LINE
ZONE 4
4321
4321
LLM-1
TB1
TB2
-
----
-
NOTES
1. All wiring must be in accordance
with Article 760 of NEC or local
building codes.
2. All output circuits are power
limited.
3. Leased Line circuit rating:
24 VDC open circuit filtered
full wave
4. External circuit resistance:
2k to 5k ohms
5. Rated Current: 3mA to 9mA,
alarm / supervisory.
6. Polarity shown in active state.
7. Lease Line circuits are not
supervised.
8. LLM-1 module is required.
9. Load must be compatible polarity reversal labeled
Remote Station Receiver Unit.
10. Input voltage sources can be daisy-chained.
11. Any circuit may be used.
12. Minimum Emergency Power:
60 hours standby
5 minute alarm
13. Intended for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings.
14. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installa-
tion Instructions for details on the separation of power limited and non-power limited wiring.