Zone Wiring
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory: 4mA max
Output Zone Active: 96 Watts max / zone
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Positive or negative ground fault detected at <40K ohms for
terminals 1-16.
Figure 12
ZIC-4A Two-Channel Audio Wiring
12345678
910111213141516
+
+
+
+
NC
NC
NC
NC
-
---
17 18 19 20 21 22 23 24
STYLE Y
(CLASS B)
STYLE Z
(CLASS A)
ONE SLOT OF CC-5
24K,
1W
5%
24K,
1W
5%
ZONE 4
ZONE 3
+
-
+
-
+
-
+
-
+
+
--
TO NEXT
ZIC-4A
CHANNEL A
CHANNEL B
AUDIO FROM PREVIOUS
ZIC-4A OR FROM ZAC-40/
ZAM-180 TERMINALS
1A AND 1B OR 2A AND 2B
24K,
1W
5%
ZONE 1 ZONE 2
STYLE Z
CLASS A
24K,
1W
5%
STYLE Y