EasyManua.ls Logo

Siemens ZIC-4A - Single-Channel Audio Wiring

Siemens ZIC-4A
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Siemens Industry, Inc.
Building Technologies Division
P/N 315-033050-1518
12345678
910111213141516
+
+
+
+
NC
NC
NC
NC
-
---
17 18 19 20 21 22 23 24
ZONE 2
STYLE Y
(CLASS B)
STYLE Z
(CLASS A)
ONE SLOT OF CC-5
24K,
1W
5%
24K,
1W
5%
24K,
1W
5%
ZONE 4
ZONE 3
STYLE Y
CLASS B
ZONE 1
STYLE Z
CLASS A
+
-
+
-
+
+
--
TO NEXT ZIC-4A
AUDIO FROM PREVIOUS
ZIC-4A OR FROM
ZAM-180 TERMINALS
1A AND 1B OR 2A AND 2B
ZAC-40/
24K,
1W
5%
NOTES
1. All wiring must be in accordance with
Article 760 of NEC or local building
codes. Wiring for each zone can
either be Class A or Class B.
2. All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory:
4mA max
Output Zone Active:
96 Watts max / zone
4. EOL resistor, 24k ohms,
1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. For a list of Compatible Notification
Appliances, refer to P/N 315-096363.
7. Refer to CAB1/CAB1R (P/N 315-
0330007) and CAB2-BB/CAB3-BB (P/
N 315-033009) Installation Instruc-
tions for details on the separation of
power limited and non-power limited
wiring.
8. Positive or negative ground fault
detected at <40K ohms for
terminals 1-16.
Figure 13
ZIC-4A Single-Channel Audio Wiring

Related product manuals