CCP 611 C-DIAS PROSESSOR MODULE
Page 16 27.03.2020
7 Display
The CCP 611 processor module has a 2-digit decimal display (7-segment display) for the
following functions:
When configuring the processor module, the parameters are shown in the display.
If an error occurs while running the program or no valid user program is found, the dis-
play shows an error message. Thereby, "Er" (error) and the error code alternate in the
display. The same error code is also shown in the LASAL status line.
While running the program, the display can be used to show digits using the system
variable _cpuDisplay. Valid values are 0 to 255; values over 99, however, are not
shown and the display remains dark.