SIKA TD 32500 Operating Manual
5.2.6 Programming frequency divider
You can only carry out this configuration, if TD 32500 is equipped with a
frequency divider output.
With this programming you determine the factor by which the input pulse
rate generated by the flow sensor is divided in order to allow output at a
smaller pulse rate.
Note: If the built-in flow sensor provides for example a pulse rate of
855 pulses/liter (printed on type plate) and a factor "6" is
programmed, a pulse rate of 142,5 pulses/liter is quoted at the outlet.
P
roceed as follows:
• Switch over to configuration menu.
• Press the
key until the message
„SET PULSE DIVIDE – NO“ appears.
• Switch with the ▲ key to „YES“ and confirm with the
key.
• The message appears „VALUE OK ?“ together with the last entered
fa
ctor.
• Switch with the ▲ key to „CHANGE VALUE ?“ and confirm with the
key.
• A cursor appears. Set with the ▲ key the respective digit of the new
factor and confirm it with the
key.
5.2.7 Quit configuration menu
• The message „QUIT CONFIG – NO“ appears.
• Switch with the ▲ key to „YES“ and confirm with the
key.
• The configuration menu is quit. TD 32500 switches back to
m
easurement operation.
• If you confirm with "NO", the system returns to the beginning of the
configuration menu.
Note: By simultaneous pressing the keys ▲ and
at any position in
the configuration menu, the instrument switches to the menu item
"Quit configuration menu".