Chapter 4. Programming the DACT
4-5
4. Press the <NEXT> key. The prompt for the Test Report
Time appears.
Test Report Time
This option specifies the time at which the Test Report Event
is sent to the supervising station. Time is set in 24 hour, mil-
itary format.
<ENTER> = Accept
Opt: [Test Rpt Time]
1. Press <ENTER>.
Test Rpt Time
[02] : 00
2. Use the NEXT and PREV keys to increment or decre-
ment the hour setting (two digits on left). Use the right
arrow key to move the cursor to the minutes (two digits
on right). Use the NEXT and PREV keys to increment
or decrement the minutes setting.
3. Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
4. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
5. Press the <EXIT/CLEAR> key. The prompt for setting
DACT options reappears. Press the <NEXT> key to
access either the CID Points or Event Codes menus.
Programming Contact ID (CID)
Points
Follow the procedure below only if the DACT is using the
Contact ID (CID) reporting format. CID reporting format
requires you to specify the group and Contact ID for each
point, but there is no need to specify the type of event with
the CID format. This information is automatically derived
from the point’s function type.
Note: Default CID point values are provided in the panel.
Before changing these values, please contact an authorized
representative at the supervising station.
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
1. Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose CID Points.
<ENTER>=Accept
DACT: [CID Points]
2. Press <ENTER>. A prompt similar to the following
appears.
[Garage IDC1]
GRP: 01 ID: 001
This prompt consists of the following fields.
Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point.
Grp. A 2-digit number used to group associated
devices together.
ID (Contact ID). A 3-digit number used to identify
a specific point/device.
3. For each point, use the right arrow key to move between
the digits of the GRP and ID fields. Use the <NEXT>
and <PREV> keys to increment or decrement the value
of a digit.
4. To choose another point, press the right arrow key until
the cursor is on the top line (custom label) of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another point and then repeat Step 3.
Table 4-1 Default CID Event Codes
Function Type Fire Supervisory Trouble
FIRE 110 - 330
WATER 113 - 330
HEAT 114 - 330
DUCT 116 - 330
PULL 115 - 330
SMOKE 111 - 330
SO - 200 330
WSO 110 200 330
SUPV - 200 330
UTIL - - 330
TROUBLE - - 330
VSMOKE 111 - 330
LATSUPV - 200 330
STYLEC 110 - 330
OTHER TRBL* - - 330
Table 4-1 Default CID Event Codes