Chapter 4. Programming the DACT
4-6
5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
GRP: [01] ID:001
6. Press <ENTER>. The prompt shown in Step 1 appears.
Programming Event Codes
Follow the procedure below only if the DACT is using the
3/1 or 4/2 reporting format.
1. Follow the steps in “Accessing DACT Menu,” earlier in
this chapter. Use the <NEXT> or <PREV> keys to
choose Event Codes.
<ENTER>=Accept
DACT: [Event Codes]
2. Press <ENTER>. A prompt similar to the following
appears.
[FIRE ALARM]
Code: A1
3. For each code, use the right arrow key to move between
the letter/digit of the Code field. Use the <NEXT> and
<PREV> keys to increment or decrement the value of a
letter or digit. See Table 4-2 for a list of Event types and
their corresponding codes.
4. To choose another code to edit or verify, press the right
arrow key until the cursor is on the top line of the
prompt. Use the <NEXT> and <PREV> keys to scroll
to another code and then repeat Step 3.
5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
Code: A1
6. Press <ENTER>. The prompt shown in Step 1 appears.
Note: Event codes for SIA and BFSK are non-editable.
Saving Changes
When DACT programming is complete, press the EXIT/
CLEAR key until the following prompt is shown.
[Cont] Dscrd Save
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
• Cont - continues the edit session.
• Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
• Save - saves your edit changes
Note: Both discard and save restart the panel.
Table 4-2 Event Categories and Codes
Event 3/1 BFSK 4/2 SIA
Fire Alarm 1 11 A1 FA1
Supervisory 3 33 A3 SS3
Trouble 4 F4 A4 FT4
Fire Restoral E E1 71 FR1
Supervisory
Restoral
E E3 73 SJ3
Trouble Restoral E E4 74 FJ4
Phone Line 1
Trouble
F FB 31 LT1
Phone Line 1
Restoral
E EB 35 LR1
Phone Line 2
Trouble
F FC 32 LT2
Phone Line 2
Restoral
E EC 36 LR2
AC Failure F FA 6A AT0
AC Restoral E EA 7A AR0
Auto Test Report E EE 3A RP0
Manual Test
Report
E EE 3A RX0
Off-normal at
test
F F8 33 YX0
Table 4-2 Event Categories and Codes
Event 3/1 BFSK 4/2 SIA
Technical Manuals Online! - http://www.tech-man.com