EasyManua.ls Logo

Simplex 4006-9101 - Operating; Normal Operation; Lamp Test; Abnormal Conditions

Simplex 4006-9101
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-1
Normal Operation
The panel’s operator interface shows the following under normal condi-
tions:
Green AC power LED is on steady
All other panel indicator LEDs are off
Front panel LCD shows the following:
SYSTEM NORMAL
1:45:07 pm 3/10/04
Lamp Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key and then pressing ENTER. All LEDs ener-
gize and all LCD segments are written to.
Abnormal Conditions
Abnormal conditions are indicated on the panel by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervi-
sory. If the “Display First Alarm” option is selected, the display pro-
vides information about the first, highest-priority alarm in the system
without operator intervention. If “Display First Alarm” is not selected, a
screen showing the overall system status is shown:
FIRE | SUPV | TRBL
02 | 00 | 00
When the appropriate Acknowledge key is pressed, the tone-alert turns
off and the indicator LED illuminates steady, indicating that the operator
has acknowledged all events in that category. The first abnormal point
in that category is then shown on the display:
CORE 1 MEZZANINE
In This Chapter
Normal Operation. . . . . . . . . . . . . . . . . . . . . . 7-1
Lamp Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Abnormal Conditions . . . . . . . . . . . . . . . . . . . 7-1
Silencing Alarms . . . . . . . . . . . . . . . . . . . . . . 7-2
System Reset. . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Viewing/Clearing Historical Logs . . . . . . . . . . 7-2
Viewing and Controlling Points. . . . . . . . . . . . 7-3
Manually Activating a NAC/Relay . . . . . . . . . 7-4
Enabling or Disabling Points . . . . . . . . . . . . . 7-4
Control Functions . . . . . . . . . . . . . . . . . . . . . . 7-4
Setting the Time and Date . . . . . . . . . . . . . . . 7-5
Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
WalkTest. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Chapter 7. Operating
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Related product manuals