Chapter 2. Installation and System Checkout
2-8
Auxiliary Relay Wiring
All wiring must be 18 AWG (minimum) to 12 AWG
(maximum). Conductors must test free of all grounds
and stray voltages before connection to appliances,
devices, and panel.
Contact rating: 30VDC @ 2A, 0.35 power factor
If using expansion relay module, set EXP RELAY sys-
tem option to ON.
Each relay is selected for normally closed or normally
open operation. Shunt jumper setting (see figure) selects
desired contact.
Relay 1 is programmable. Its default operation is Com-
mon Alarm - On Until Reset. Jumper is P1.
Relay 2 is a normally energized, common trouble relay.
The jumper settings noted in the figure account for the
relay being normally energized. Jumper is P2.
When the panel is completely powered off, the trouble
relay will be in the “Off Normal” state.
All wiring is unsupervised.
Figure 2-8 Relays on Main System Board