EasyManua.ls Logo

Simplex 4006-9101 - Common LED Applications; Saving Changes

Simplex 4006-9101
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5. Programming Annunciator LEDs
5-7
6. When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the refer-
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. For example:
Type: BZONE Fire
IDC10
7. Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8. Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9. Press <ENTER>. A prompt appears, asking you to con-
firm the changes.
10. Press <ENTER> to confirm the changes.
Common LED Applications
Common applications for programmable LEDs are:
Earth Fault Detect LED. This LED tracks whether the
panel’s Earth fault system point is active or not. If the
point enters a trouble state (i.e., there is an Earth fault),
the yellow LED illuminates. Program the LED as fol-
lows:
- Make sure the color is yellow
- Select the "TRBL" mode
- Select 17-06 as the reference point
Waterflow LED, which illuminates if a device with the
function type WATER or WSO activates. Program the
LED as follows:
- Make sure the LED color is red
- Select the "FIRE" mode
- Select 22-101 as the reference point
City/DACT Disconnect (required for Canadian panels).
This LED tracks whether the City/DACT Disconnect
system point is active or not. If the point turns ON (i.e.,
either the city circuit or DACT has been disconnected),
the yellow LED illuminates. Program the LED as fol-
lows:
- Make sure the color is yellow
- Select the "ON" mode
- Select 18-14 as the reference point
Signal Silence Inhibit Enabled (required for Canadian
panels). This LED tracks whether the Signal Silence
Inhibit Enabled system point is active or not. If the point
turns ON (i.e., Signal Silence Inhibit system option is
set to ON), the yellow LED illuminates. Program the
LED as follows:
- Make sure the color is yellow
- Select the "ON" mode
- Select 18-35 as the reference point
Saving Changes
When Annunciator programming is complete, press the
EXIT/CLEAR key until the following prompt is shown.
[Cont] Dscrd Save
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
Cont - continues the edit session.
Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
Save - saves your edit changes
Note: Both discard and save restart the panel.