Chapter 5. Programming Annunciator LEDs
5-5
LED Card 5, Pt 1
Fn: [Edit Mode]
4. Press <ENTER>. A prompt similar to the following
appears.
Mode Prg - Output
[TRBL] 15-10
5. Use the <NEXT> and <PREV> keys to scroll through
the available modes. As you scroll through the modes,
the default reference address for the mode appears to the
right of the mode. Refer to Table 5-3 for a list of the
available modes.
6. When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the refer-
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. Refer to Table 5-4 for a list of
common reference points. For example:
Type: BZONE Fire
IDC10
7. Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8. Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9. Press <ENTER>. A prompt appears, asking you to con-
firm the changes.
10. Press <ENTER> to confirm the changes.
Table 5-3 LED Modes
Mode Description
FIRE
Output activates when referenced point is in
an Alarm condition.
SUPV
Output activates when referenced point is in a
Supervisory condition.
TRBL
Output activates when referenced point is in a
Trouble condition.
DISA
Output activates when the referenced point is
Disabled.
ON
Output activates when the state of the refer-
ence point is ON.
OFF
Output activates when the state of the refer-
ence point is OFF.
LF
Output activates when any point is in an
alarm condition.
LS
Output activates when any point is in a super-
visory condition.
LT
Output activates when any point is in a trou-
ble condition.
Table 5-4 Common LED Reference Points
Reference
Point
Description
IDCs 1-10
Separate reference point for each IDC. State
monitored determined by selected LED
mode.
Aux Relays 1
and 2
Separate reference point for each relay. State
monitored determined by selected LED
mode.
City/DACT Dis-
connect (18-14)
Separate reference point for disconnect and
trouble. Typical use is to monitor the ON state
of either point.
City Trouble
Control Bypass
Separate reference point for each type of
bypass.Typical use is to monitor the ON state
of any of the points.
Elevator Bypass
Door Bypass
List - General
Alarm Points
List contains all zones with FIRE, VERIF, or
STYLEC function type. Monitoring the Fire or
Trouble state of this list allows you to illumi-
nate an LED when any zone in the list enters
an alarm or trouble state. Select either FIRE
or TRBL as the mode.
List - Waterflow
Zones
List contains all zones with WATER or WSO
function type. Monitoring the Fire or Trouble
state of this list allows you to illuminate an
LED when any zone in the list enters an
alarm or trouble state. Use output mode to
select which state (Fire, Trouble) is moni-
tored.
List - Sprinkler
Zones
List contains all zones with SO or WSO func-
tion type. Monitoring the Fire, Trouble, or
Supervisory state of this list allows you to illu-
minate an LED when any zone in the list
enters an alarm, trouble, or supervisory state.
Select either FIRE, TRBL, or SUPV as the
mode.
Alarm Group
1 -99
Separate list for each alarm group. Monitoring
the Fire, Supervisory, Trouble, or ON state of
an alarm group list allows you to illuminate an
LED if any point in the group enters the fire,
trouble, supervisory, or ON state. Use output
mode to select state monitored.
Table 5-3 LED Modes
Mode Description