Installation notes:
All wiring is 18 AWG (0.8321 mm
2
), unshielded twisted pair.
Maximum wire distance: 2,500 ft (762 m) from ES Net Digital Audio Controller primary to the first Digital Audio Riser Interface Card (DARIC) primary.
Maximum distance between subsequent nodes: 2,500 ft (762 m).
Maximum line distance and capacitance between nodes: 18 AWG (0.8321 mm
2
): 40 Ohms maximum, 0.055 μF maximum.
All wiring that leaves the building requires the 2081-9044 Overvoltage Protector at each entry or exit to the building. A maximum of two overvoltage
protectors are allowed for each DAR link. Each 2081-9044 adds 6 Ohms and 0.006 μF. Connect the DAR shield according to the 2081-9044
instructions.
Wiring must be free of all grounds.
The maximum number of digital interface cards per digital audio riser is 31.
All riser wiring is supervised and power-limited.
Audio wiring is not to be mixed in the same jacket with other wiring including other audio wiring.
If you use shielded wire indoor installations, leave the shield floating by cutting and taping the shield at both ends.
For installations outside of these guidelines, contact your sales support channel.