All wiring that leaves the building requires the 2081-9044 Overvoltage Protector at each entry or exit to the building. You can use a maximum of
two overvoltage protectors for each DAR link. Each 2081-9044 adds 6 Ohms and 0.006 μF. Connect the DAR shield according to the 2081-9044
instructions.
Wiring must be free of all grounds.
The maximum number of digital interface cards for each digital audio riser is 31.
All riser wiring is supervised and power-limited.
You must not mix audio wiring in the same jacket with other wiring including other audio wiring.
If you use shielded wire indoor installations, leave the shield floating by cutting and taping the shield at both ends.
For installations outside of these guidelines, contact your sales support channel.
page 19 579-1408 Rev. B
ES Net Digital Audio Controller Installation Instructions