CPU Bay Module Details
Master Controller and Motherboard:
Mounts in Slot 4 of a two slot motherboard (Slots 3 and 4
of the Master Controller Bay) and provides one Style 4 or
Style 7, RUI communications channel, available at Slot 4
RUI communications controls up to 31 devices per master
controller (on one or multiple RUI channels); devices
include: MINIPLEX transponders, 4603-9101 LCD
Annunciators, 4602-9101 Status Command Units (SCU),
4602-9102 Remote Command Units (RCU), 4602 Series
LED Annunciator Panels, 4100 Series 24 I/O and
LED/Switch modules, and remote mount 4009 TPS units
Up to four RUI channels are supported; use up to three
4100-1291 RUI expansion modules as required
Optional Service Modem 4100-6030 mounts onto the
master controller board with its own on-board connections
Slot 3 of the motherboard is primarily for the 4100-6078
Network Interface Board with media modules, and
secondarily for the 4100-6038 Dual RS-232 Board
(4100-6038 is required for 2120 System connections)
System Power Supply:
(see page 8 for more detail)
Rating is 9 A total with “Special Application” appliances;
4 A total for “Regulated 24 DC” appliance power
Outputs are power-limited, except for the battery charger
Provides system power, battery charging, auxiliary power,
auxiliary relay, earth detection, on-board IDNet
communications channel for 250 points, three on-board
NACs, and provisions for either an optional City Connect
Module or an optional Alarm Relay Module
IDNet SLC Output provides Class B or Class A
communications for up to 250 addressable devices (as
described on page 4)
System Power Supply (Continued):
Three, 3 A On-Board NACs, conventional reverse
polarity operation; rated 3 A for Special Application
appliances and 2 A for Regulated 24 DC power, with
electronic control and overcurrent protection; selectable
as Class B or Class A, and for synchronized strobe or
SmartSync horn/strobe operation over two wires
NACs can be selected as auxiliary power outputs
derated to 2 A for continuous duty; the total auxiliary
power output per SPS is limited to 5 A
Battery Charger is dual rate, temperature compensated,
and charges up to 50 Ah sealed lead-acid batteries
mounted in the battery compartment (33 Ah for single
bay cabinets); also is UL listed for charging up to
110 Ah batteries mounted in an external cabinet (see
data sheet S2081-0012 for details)
Battery and Charger Monitoring includes battery
charger status and low or depleted battery conditions;
status information provided to the master controller
includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current,
and individual NAC currents
2 A Auxiliary Power Output is selectable for detector
reset, door holder, or coded output operation
Auxiliary Relay is selectable as N.O. or N.C., rated 2 A
@ 32 VDC, and is programmable as a trouble relay,
either normally energized or normally de-energized, or
as an auxiliary control
Optional City Connect Module (4100-6031, with
disconnect switches, or 4100-6032, without disconnect
switches) can be selected for conventional dual circuit
city connections
Optional Alarm Relay Module (4100-6033) provides
three Form C relays that are used for Alarm, Trouble,
and Supervisory, rated 2 A resistive @ 32 VDC
Master Controller and Expansion Bay Selection* (Canadian models have low battery cutout)
Model Model Type and Listing Description Supv. Alarm
4100-9111 120 VAC Input UL
4100ES Master Controller Assembly with LCD and
operator interface, 9 A system power supply/battery
charger (SPS), 250 point IDNet interface, 3 NACs,
auxiliary relay, and external RUI communications interface
373 mA 470 mA
4100-9112 English
120 VAC, Canadian ULC
4100-9113 French
4100-9211 220-240 VAC Input UL
4100-9131 120 VAC Input UL
4100ES Master Controller Assembly, no display, no
operator interface, 9 A system power supply/battery
charger (SPS), 250 point IDNet interface, 3 NACs,
auxiliary relay, and external RUI communications interface
363 mA 425 mA
4100-9132 English 120 VAC, Canadian ULC
4100-9230 220-240 VAC Input UL
4100-9121
(not ULC
listed)
Redundant Master Controller, two bay assembly; top bay contains LCD and operator interface,
CPU card assembly, and 4100ES, 9 A system power supply/battery charger (SPS); second bay
contains CPU card in Slot 2, and LCD and operator interface; 120 VAC, 60 Hz input;
NOTE: RUI connections require use of 4100-1291 RUI expansion modules
718 mA 937 mA
4100-2300
Expansion Bay Assembly; order for each required expansion bay (not required for 4100-9121)
4100-2303 Legacy Module Stabilizer Bracket, used when expansion bays have legacy slot style modules
Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels*
Model Panel Type Includes
4100-7150 1000 pt 4100 (4100+) New Master Controller and 4100ES user interface door assembly with Ethernet connection
4100-7152 512 pt 4100 Same as 4100-7150 plus includes a Universal Power Supply
4100-7158
1000 pt 4100 (4100+)
or 4100U
New Master Controller with Ethernet Connection Upgrade Kit; for 4100+ without LCD and
operator interface, or 4100U with or without LCD and operator interface
4100-2301
Expansion Bay Upgrade Kit for mounting 4100ES style (4” x 5” modules) in existing 4100 style panels;
Note: When using this kit to upgrade a 4100+ transponder, a 4100-0620 Transponder Interface Card (TIC) is also
required for communications to the 4100ES module
* For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045. (Continued on next page)
5 S4100-0031-21 12/2012
Master Controller Selection Information