CPU Bay Module Details
Master Controller and Motherboard:
Mounts in Slot 4 of a two slot motherboard (Slots 3 and 4
of the Master Controller Bay) and provides one Style 4 or
Style 7, RUI communications channel, available at Slot 4
RUI communications controls up to 31 devices per master
controller (on one or multiple RUI channels); devices
include: MINIPLEX transponders, 4603-9101 LCD
Annunciators, 4602-9101 Status Command Units (SCU),
4602-9102 Remote Command Units (RCU), 4602 Series
LED Annunciator Panels, 4100 Series 24 I/O and
LED/Switch modules, and remote mount 4009 TPS units
Up to four RUI channels are supported; use up to three
4100-1291 RUI expansion modules as required
Optional Service Modem 4100-6030 mounts onto the
master controller board with its own on-board connections
Slot 3 of the motherboard is primarily for the 4100-6078
Network Interface Board with media modules, and
secondarily for the 4100-6038 Dual RS-232 Board
(4100-6038 is required for 2120 System connections)
System Power Supply:
(see page 8 for more detail)
Rating is 9 A total with “Special Application” appliances;
4 A total for “Regulated 24 DC” appliance power
Outputs are power-limited, except for the battery charger
Provides system power, battery charging, auxiliary power,
auxiliary relay, earth detection, on-board IDNet
communications channel for 250 points, three on-board
NACs, and provisions for either an optional City Connect
Module or an optional Alarm Relay Module
IDNet SLC Output provides Class B or Class A
communications for up to 250 addressable devices (as
described on page 4)
System Power Supply (Continued):
Three, 3 A On-Board NACs, conventional reverse
polarity operation; rated 3 A for Special Application
appliances and 2 A for Regulated 24 DC power, with
electronic control and overcurrent protection; selectable
as Class B or Class A, and for synchronized strobe or
SmartSync horn/strobe operation over two wires
NACs can be selected as auxiliary power outputs
derated to 2 A for continuous duty; the total auxiliary
power output per SPS is limited to 5 A
Battery Charger is dual rate, temperature compensated,
and charges up to 50 Ah sealed lead-acid batteries
mounted in the battery compartment (33 Ah for single
bay cabinets); also is UL listed for charging up to
110 Ah batteries mounted in an external cabinet (see
data sheet S2081-0012 for details)
Battery and Charger Monitoring includes battery
charger status and low or depleted battery conditions;
status information provided to the master controller
includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current,
and individual NAC currents
2 A Auxiliary Power Output is selectable for detector
reset, door holder, or coded output operation
Auxiliary Relay is selectable as N.O. or N.C., rated 2 A
@ 32 VDC, and is programmable as a trouble relay,
either normally energized or normally de-energized, or
as an auxiliary control
Optional City Connect Module (4100-6031, with
disconnect switches, or 4100-6032, without disconnect
switches) can be selected for conventional dual circuit
city connections
Optional Alarm Relay Module (4100-6033) provides
three Form C relays that are used for Alarm, Trouble,
and Supervisory, rated 2 A resistive @ 32 VDC
Master Controller and Expansion Bay Selection* (Canadian models have low battery cutout)
Model Model Type and Listing Description Supv. Alarm
4100-9111 120 VAC Input UL
4100ES Master Controller Assembly with LCD and
operator interface, 9 A system power supply/battery
charger (SPS), 250 point IDNet interface, 3 NACs,
auxiliary relay, and external RUI communications interface
373 mA 470 mA
4100-9112 English
120 VAC, Canadian ULC
4100-9113 French
4100-9211 220-240 VAC Input UL
4100-9131 120 VAC Input UL
4100ES Master Controller Assembly, no display, no
operator interface, 9 A system power supply/battery
charger (SPS), 250 point IDNet interface, 3 NACs,
auxiliary relay, and external RUI communications interface
363 mA 425 mA
4100-9132 English 120 VAC, Canadian ULC
4100-9230 220-240 VAC Input UL
4100-9121
(not ULC
listed)
Redundant Master Controller, two bay assembly; top bay contains LCD and operator interface,
CPU card assembly, and 4100ES, 9 A system power supply/battery charger (SPS); second bay
contains CPU card in Slot 2, and LCD and operator interface; 120 VAC, 60 Hz input;
NOTE: RUI connections require use of 4100-1291 RUI expansion modules
718 mA 937 mA
4100-2300
Expansion Bay Assembly; order for each required expansion bay (not required for 4100-9121)
4100-2303 Legacy Module Stabilizer Bracket, used when expansion bays have legacy slot style modules
Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels*
Model Panel Type Includes
4100-7150 1000 pt 4100 (4100+) New Master Controller and 4100ES user interface door assembly with Ethernet connection
4100-7152 512 pt 4100 Same as 4100-7150 plus includes a Universal Power Supply
4100-7158
1000 pt 4100 (4100+)
or 4100U
New Master Controller with Ethernet Connection Upgrade Kit; for 4100+ without LCD and
operator interface, or 4100U with or without LCD and operator interface
4100-2301
Expansion Bay Upgrade Kit for mounting 4100ES style (4” x 5” modules) in existing 4100 style panels;
Note: When using this kit to upgrade a 4100+ transponder, a 4100-0620 Transponder Interface Card (TIC) is also
required for communications to the 4100ES module
* For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045. (Continued on next page)
5 S4100-0031-21 12/2012
Master Controller Selection Information

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)