7 S4005-0001-9 3/2009
Electrical
102–132 VAC, 60 Hz; 2 A maximum
Standard Panel Input (Switch Selectable)
204–264 VAC, 50/60 Hz; 1 A maximum
4 A for Special Application Notification Appliances
Main Power Supply Output*
2 A for Regulated 24 VDC Notification Appliances
102–132 VAC, 60 Hz; 3 A maximum
Expansion Power Supply Input (Switch Selectable)
204–264 VAC, 50/60 Hz; 1.5 A maximum
5 A for Special Application Notification Appliances
Expansion Power Supply Output*
2 A for Regulated 24 VDC Notification Appliances
NAC Operation, Per Circuit 2 A maximum
Special Application Appliances
Simplex 4901, 4903, 4904, and 4906 Series non-addressable horns, strobes,
and combination horn/strobes and speaker/strobes (contact your Simplex
product representative for compatible appliances)
Regulated 24 DC Appliances
Power for other applicable UL listed appliances; use associated external
synchronization modules where required
Input Mode Dry Contact, supervised with 2.2 kΩ end-of-line resistor 4081-9001
8 Circuit I/O Module
Output Mode 24 VDC, 150 mA, open collector
Relay Operation, N.O./N.C. 2 A @ 32 VDC
Resettable 4-Wire Smoke Detector Power 24 VDC, 500 mA, open collector
Auxiliary Power Connections (two taps) 2 A; maximum each tap, power-limited; 18.7 to 32 VDC
Wiring Terminal Blocks Pluggable type, wire size is 18 to 12 AWG (0.82 mm
2
to 3.31 mm
2
)
Operating Temperature 32° F to 120° F (0° C to 49° C)
Wiring and
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 100°F (38° C)
*NOTE: Power supply output currents listed are entirely available for NAC appliances and auxiliary equipment. 4005 modules are
powered from separate circuits.
See Field Wiring Diagram 841-990 and Installation Instructions 574-068 for additional detail.
Module
Supv.
(mA)
Quantity
Supv.
Total
Alarm
(mA)
Quantity
Alarm
Total
4005-9101 & -9102
Includes 2, 4005-9804 & 1, 4005-9805 135 293
4005-9101C & CF
Includes 2, 4005-9804 & 1, 4005-9805 168 328
4005-9150
Includes 2, 4005-9824 & 1, 4005-9805 141
Select
one
330
Select one
Separate Modules; Standard, Optional, and Expansion; see NOTES ( ) below
4005-9806, Class A Adapter 1 x = 33 x =
4005-9807, Expansion Power Distribution Module 1 x = 1 x =
4005-9809, 1 Circuit Remote Station/City Connect 11 x = 22 x =
4005-9813, Expansion Power Supply 12 x = 12 x =
4005-9803, 2 IDC, Low Current, and 2 NAC/Relay (1, 2, 3, 4, 5) 10 x = 34 x =
4005-9804, 4 IDC, Low Current (1, 2, 3) 22 x = 57 x =
4005-9805, 4 NAC/Relay (5) 8 x = 53 x =
4005-9808, 8 Circuit I/O Module 1 x = 1 x =
4005-9824, 4 IDC, High Current (1, 2, 4) 28 x = 94 x =
Internal DACT (aftermarket PID 4005-9810) (6) 35 x = 50 x =
Total, 4005 Modules
Total, 4-Wire Detector Power + +
Total, Other Auxiliary Power + +
Total, Notification Appliance Power + +
† Standard panels and 4005-9150 include
IDC loop currents for both supervisory
and alarm.
Total Supervisory Current Total Alarm Current
NOTES:
1. IDC supervisory currents include loop currents of 2 mA/circuit for “low” current IDCs and 3 mA/circuit for “high” current IDCs.
2. IDC Alarm currents, add as required. Low current IDCs = 13 mA/circuit; High current IDCs = 50 mA/circuit.
3. Add 8 mA supervisory current per SC, WSC point used.
4. Add 10 mA supervisory current per SC point used.
5. Add 8 mA supervisory current per circuit if used as auxiliary relay and programmed for normally on.
6. DACT Current is 50 mA when reporting.
Battery Requirements