Special functions
Sprinkler function:
DIP 9 On - a special function comes in use where sprinkler systems are installed. With this function activated, the actuator
output closes, if smoke-/heat detector input is activated.
If the re switch is activated, the actuator output opens.
Weekly open/close:
DIP 7 On - the motor output opens shortly (3 seconds) once a week and closes immediately after -
This function is used to give the right tension on the smoke vents to keep them airtight.
Function of heat detector in LIP:
DIP 3 On - a heat detector 70-100° can be mounted in each LIP. If the temperature is exceeded, the control unit goes into
alarm status and the opening system opens.
Special mode:
DIP 12 On - possible to use comfort switch also during line fault, low batt., no AC, Alarm only as long as re input is active
or detector is activated.