Technical Data SMA Solar Technology AG
82 SMC9-11TLRP-IEN100640 Installation Guide
11 Technical Data
11.1 Sunny Mini Central 9000TL / 10000TL / 11000TL
SMC
9000TL-10
SMC
10000TL-10
SMC
11000TL-10
PV generator connection data
Max. PV input voltage U
PV 0
700 V
a)
(Based on -10 °C cell temperature)
Input voltage, MPP range U
PV
333 V ... 500 V DC
PV start voltage, adjustable U
PV Start
400 V 400 V 400 V
Max. input current I
PVMax
28 A 31 A 34 A
Max. input power P
DC
9300 W 10350 W 11400 W
Voltage ripple Upp < 10 % of the input voltage
Internal consumption during
operation
< 8 W
a)The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, may not exceed the maximum input
voltage.
Grid connection data
AC nominal power P
ACNom
9000 W 10000 W 11000 W
Max. AC power P
ACMax
9000 W 10000 W 11000 W
Nominal AC current I
ACNom
40 A 44 A 48 A
Max. AC current I
ACMax
40 A 44 A 48 A
Max. fuse protection 80 A
Harmonic distortion of output current
(at K
Ugrid
< 2 %, P
AC
> 0.5 P
ACNom
)
K
IAC
< 4 %
Nominal operating voltage U
ACnom
220 V / 230 V / 240 V
Voltage range
(extended operating range)
U
AC
180 V ... 260 V
Nominal operating frequency f
ACnom
50 Hz / 60 Hz
Frequency range
(extended operating range)
f
AC
50 Hz: 45.5 Hz ... 54.5 Hz
60 Hz: 55.5 Hz ... 64.5 Hz
Power factor (at nominal output
power)
cos ϕ 1
Overvoltage category III
Test voltage (50 Hz) 2.15 kV
Test surge voltage 4 kV (serial interface: 6 kV)
Internal consumption in night mode 0.15 W