6 Electrical Connection
SMA Solar Technology AG
Operating manualEVCxx-10-BE-en-1026
6.2 Mounting the Connection Cap
Requirements:
☐ Only use the supplied cable glands.
Procedure:
1. Attach the cable gland for connecting the utility grid to the terminal cover:
• If the AC cable has a diameter of 11mm to 17mm, insert the M25 cable gland into the
opening of the terminal cover and tighten.
• If the AC cable has a diameter of 15mm to
21mm, insert the cable gland extension into
the opening of the terminal cover and tighten.
Then insert the M32 cable gland into the cable
gland extension and tighten.
2. Attach the cable gland for connecting the charging cable to the terminal cover:
• Insert the M25 cable gland with bending
protection spiral into the opening of the
terminal cover and fasten it from inside with the
counter nut.
3. Put the terminal cover on the enclosure and tighten
the 3 screws loosely in the given order, so that the
terminal cover still has some play (TX20).